RKI-500

Purpose

The relay of control of isolation of RKI-500 is intended for control of resistance of isolation in single-phase and three-phase networks of an alternating voltage to 450 V with a frequency of 50 Hz with the isolated neutral.

At deterioration of isolation the internal system of the sound and light notification joins, and contacts of the executive relay switch.

Design of system
The RKI-500 block is executed in the case for installation on a DIN lath.
– On the forward panel of the block there are LED indicators "NETWORK", "ACCIDENT" and the buttons "TEST", "DUMPING", "Shutdown of a Sound Signal".
– In the top and lower part of the block there are terminal blocks for connection of power supply, a controlled network and other control units and alarm systems.
– Power supply of the relay can directly be carried out from a controlled network or from not stabilized source of constant voltage of =24 V, =12 V. Power-supply circuits, measurement and contact of the output relay galvanic are divided.

Technical characteristics

Parameter
Value
Supply voltage ~220±10% V, 50 Hz
=24±10% V
=12±10% V
Tension of a controlled network (the operating value) 0….450 V
Threshold value of resistance of isolation 500 kOhm
Temporary delay on turning on of the alarm system at isolation deterioration, no more 2 s
Measuring tension 12 V
he switched contact current (AC1 of 250 V) 5 А
Power consumption, no more 3 W
Overall dimensions of the block ( 4 modules ) 71 х 90 х 60 mm
Weight, no more 0.25 kg
Range of working temperatures (without condensate) -40 … +45 °С



Pict. Standard scheme of connection of the RKI-500 (220V) block