MVF-3M

Purpose

The MVF-3M module is intended for work in chains of control of power actuation mechanisms by means of three independent switched contacts of the relay in schemes of a choice of the working phase corresponding to the set parameters, and indication of various operating modes of the block

Construstion

– The MVF-3M module is executed in the plastic case for installation on a DIN lath.
– On the forward panel of the module there are handles of regulators of installation of an operating mode of the relay and indicators of inclusion of the modes and a condition of controlled parameters.
– In the lower part of the module there are terminal blocks for connection it to a network and to the scheme of management. (Pict. 1).

Technical characteristics
Parameter
Value
Rated voltage 220/380 V; 50 Hz
The switched current of contact of the internal relay (АС1 250 В)  max 16 А
Overall dimensions of the block 71 х 90 х 60 mm
Weight, no more 0,4 kg
Adjustable settings
Top threshold of shutdown of the relay «U top t.» min 230 V
Верхний порог отключения реле «U» max 270 V
Hysteresis of the top threshold (unregulated)  5 V
Lower threshold of operation of the relay «U l.t.» min 150 V
Нижний порог срабатывания реле «U l.t.» max 200 V
Temporary delay of return on the restored phase «t return» min 0 min
Временная задержка возврата на восстановившуюся фазу «t return» max 30 min
Temporary delay of turning on of the relay when switching on a phase with a rated voltage «t turn on» min 0 s
Временная задержка включения реле при переключении на фазу с номинальным напряжением «t turn on.» max 10 s
Temporary delay of shutdown of the chosen phase at operation on the lower threshold «t turn off l.t.»  min
0 s
Temporary delay of shutdown of the chosen phase at operation on the lower threshold «t turn off l.t.»  max
10 s
Hysteresis of the lower threshold «DUн.п» min 5 V
Hysteresis of the lower threshold «DUн.п» max 20 V




Рис.1. Standard scheme of connection of MVF-3M. It is necessary to include a spark extinguishing chain parallel to the actuator coil R – 51 Ом 1Вт, С – 0,1 мкФ 630 В.

Attention! Connection of power-supply circuits of coils of contactors and alarm chains (L1, L2, L3, N) to a power network to make separate wires.