RKF-3C

Purpose

The RKF-3/1-С block is intended for control of tension and current of a three-phase network and protection of the equipment sensitive to accident of a network (engines, three-phase rectifiers).

Provides:

disconnection of three-phase loading from a network at violation of an order of alternation of phases, a distortion of phases, unrationed tension on any of phases and an overload on current (control on two phases with use of transformers of current of XXX/5 A).
Design of system.

The RKF-3/1-С block is executed in the case for installation on a DIN lath.
– Has the digital display for indication of a condition of the device. Installation of parameters of work is made on the digital display.
– In the lower and top part of the block there are terminal blocks for connections of the block to a network and to the scheme of management. Power supply of the relay it is carried out directly from a controlled network.

Technical characteristics.

Parameter
Value
Rated working voltage 220/380 V; 50 Hz
Range of parameter setting of the minimum phase tension «U,(V)» turn on 150-210 V
Range of parameter setting of the minimum phase tension «U,(V)» turn off. 155-215 V
Temporary delay of shutdown of the internal P1 relay at undervoltage below the established value 0-10 s
Temporary delay of turning on of the internal P1 relay at normalization of tension 0-10 s
Range of parameter setting of the maximum phase tension of switching off «U,(V)»* 230-270 V
Time of shutdown of the P1 relay at increase of tension is more than established value, no more 0,02 s
The rated measured current on TT1-TT3 entrances (secondary current of the transformer of current) 5 А
The maximum (short-term) measured current on TT1-TT3 entrances, no more 7,5 А
Primary current of the transformer of current 5; 10; 15; 20; 25; 30; 40; 50; 60; 75; 80; 100; 150; 200; 250; 300; 400; 500 А
Temporary delay of switching off of the P2 relay at excess of rated current (corresponds to the characteristic of operation of D) Depending on the established value of frequency rate of current
Range of change of frequency rate of current** 2…10
Minimum duration of an impulse of current of an overload 5 ms
The maximum switched current of contact of the internal relay (AC1 240B mode) 10 А
Overall dimensions               (WхHхD) 71х90х60  mm
Weight 0,35 kg

ркф-3ц-вход.jpg                ркф-3ц-вход-2.jpg
Pict.Standard scheme of turning on of the relay of control of the phases RKF-3С
а) inclusion directly
б) with use of transformer current