OM-16

Purpose

The limiter of power of OM-16 is intended for control of tension and power consumption in a single-phase network and shutdowns of loading in case of tension exit for the established threshold values or excess of electricity consumption over the established value.

Design of system

– The limiter of power of OM-16 is executed in the case for installation on a DIN lath.
– On the forward panel of the block there are handles of tuning resistors, the handle of the switch of the limiter of power and NETWORK and ACCIDENT indicators.
– In the lower part of the block there are terminal blocks for connection of the block to a network and loading. (Pict. 1)

Technical characteristics

Parameter Value
Rated voltageS 220 V; 50 Hz
Limits of regulation of tension of shutdown on the top threshold «U top» min 230 V
max 270 V
Limits of regulation of tension of inclusion on the lower threshold «U low» min 150 V
max 200 V
Time of a delay of shutdown of loading on the top threshold of tension 0,1 s
Time of a delay of shutdown of loading on the lower threshold of tension 2 s
Hysteresis of the lower threshold «DU low»=U low turn-on - U low turn-off 5 %
Values of settings of restriction of current «I(А)» 2;3;4;5;6;8;10;12;14;16 А
Temporary delay of shutdown of the relay on current (unregulated) 2 min
Time of a delay of repeated inclusion of loading after shutdown on current, «t repeat» min: 4 s
max: 180 s
The maximum switched current (АС1 250 В) 16 А
Range of working temperatures (without formation of condensate) max min -10 °С
max 40 °С
Overall dimensions of the block 34 х 90 х 65 mm
Weight, no more 0,2 kg
Section of wires for connection the blockа 1,5 mm²


Pict.1. Order of connection of the relay

Оформите заявку на расчет
X
Напишите ниже о проблеме, возникшей с нашим оборудованием
{{ ELEMENTS.length }}
{{ DATA.TOTAL_SUM }} р.
: {{ item.MODEL }}
{{ item.STATUS }}
{{ item.NALICHIE }}
{{ item.PRICE }}
{{ item.OLD_PRICE }}
- +
: {{ DATA.TOTAL_DISCOUNT_SUM }}
: {{ DATA.TOTAL_SUM }}

Наверх